I=B=R Rating Data |
Flow Rate |
Steam Rate |
*Water Ratings
BTUH Per Linear Foot at Average Water Temp. Indicated |
Lbs/Hr |
Sq. Ft. |
BTU/Hr at 215° F |
170° F |
180° F |
190° F |
200° F |
210° F |
220° F |
230° F |
500 |
3.15 |
750 |
490 |
550 |
610 |
680 |
740 |
800 |
870 |
2000 |
3.15 |
750 |
520 |
580 |
640 |
720 |
780 |
850 |
920 |
I=B=R Ratings are determined from test made in accordance with the I=B=R Testing and Rating Code for baseboard type radiation,
including an allowance of 15% for heating effect permitted by the code.
"Pressure drop Ratings are available for all sizes directly from Governale Company, Inc." |
|
|
|
|